1. Introduction:
GS-OC controller is mainly used to control the work of aviation obstacle lights; In order to facilitate user installation and use,
the controller enclosure is made of lightweight, anti-oxidation aluminum alloy material, and the fully sealed waterproof structure
is suitable for outdoor working environment. The controller can control the work of the obstacle lamp and monitor the working
status of the controlled lamp, and alarm when the lamp fails, and output the alarm signal to the fault display, display the current
status of the lamp in the form of red LED, and output the dry contact alarm signal to the monitoring room.
2. Technical specifications:
Protection level:
Rated voltage: | AC220V(±15%)、DC48V | Load capacity: | 1000W |
Rated frequency: | 50HZ—60HZ | Adapt to load types: | LED light source, incandescent light source |
Power consumption | ≤5W | Monitoring output: | Dry contact |
Ambient temperature: | -40℃~70℃ | Installation size: | 306mm×65mm×M6 |
Ambient temperature: | ≤95% | Overall dimensions: | 290mm×260mm×90mm |
Altitude: | ≤4500米 | Wind resistance: | 80m/s |
IP67 | Light control sensitivity: | 50~100Lux | |
FAA classification: | L856/L857 | The alarm status displays: | Red LED indicator |
Lightning protection class: | Imax (8/20)10KA |
3. Main functions and features:
● Can control the supporting high light intensity, medium light intensity, low light intensity series aviation obstacle lights.
● Stable operation, strong anti-interference ability, anti-vibration.
● Aluminum alloy shell material, light weight, corrosion resistance.
● With a full range of surge protection devices.
● With digital monitoring function.
● Dry contact alarm function.
● Lamp working status indicator.
● Alarm status indicator.
● Power indicator.
●EI power filter, can prevent power interference caused by lamp failure.
● It has rich overcurrent protection function, which provides effective protection for lamps and controllers when lightning strikes and overload.
4. Working principle
Monitoring: The sensor detects the signal of each lamp and outputs the electrical signal to the monitoring circuit. When the signal does not match the set value, the circuit will act and output a voltage signal to control the remote alarm indicator
5. Installation dimension diagram
6.Caution
● It is forbidden to use AC or DC power supply other than rated voltage;
● Power line and monitoring line must be connected correctly according to the color before power, otherwise it will cause damage to the lamp;
● Do not short circuit the output port of the controller to avoid damage to the controller;
● The load power should not exceed the range specified in the instruction manual, otherwise it will cause fuse blowout or damage to the control module;
● The installation personnel must close the controller safety lock after the completion of the operation, otherwise it will cause water inside the controller or personal safety will be affected;
● Non-professionals do not repair the controller to avoid expanding the fault and causing life damage;
7. Use:
Buildings, airports, chimneys, Bridges, iron towers, power towers, communication towers, super tall buildings.
GS-OC Aviation Obstacle Light controller
Mainly used to control the work of aviation obstacle lights; The controller enclosure is made of light weight, anti-oxidation aluminum alloy material, and the fully sealed waterproof structure is suit
扫描二维码分享到微信